        1. APPLICATION
        GSZ2-Y series magnetic keep DC contactor is mainly used in DC working voltage is up to 48V, working current is 100A~400A circuit, for making and breaking circuit.The product is mainly used in communication power supply、uninterrupted  power supply system, also can be used for electrocar、low voltage converter、engineering machinery and other use of DC power occasion.
        Product meets a criterion GB14048.4 and IEC/EN60947-4。
        2. TYPE  AND  MEANING
        Means coil voltage
        Y means coil is magnetic keep type
        DC-1 use category rated current
        2 means design serial number
        Z means DC contactor                                         
        TIANSHUI 213 ELECTRICAL APPARATUS CO., LTD CODE
        3. PRODUCT  FEATURES
        ■  Action agency is directly operated type, contact is double breakpoints bridge type contact
        ■  Main circuit wiring should match round or mouth type cold pressing terminals
        ■  Auxiliary contacts can be convenient loaded and unloaded
        ■  Product is bistable state, contact with closing or opening position all caging by permanent magnet, big holding force, the product with good shock resistance
        ■  Coil instant power on when need movement, doesn't need power on when normal maintain, coil energy conservation and durable
        ■  When coil A1 terminal through control power supply positive pole contact is open, when A2 terminal through control power supply positive pole contact is closed
        4. WORKING  CONDITIONS  AND  INSTALLATION  CONDITIONS
        ■  Ambient air temperature is not more than +70°C,is no less than -40°C。
        ■  When temperature is +40°C, relative air humidity is not exceeding 50%, with lower temperature higher relative humidity will be permitted,in 20 may up to 90%。By the temperature change to occasionally produce dews, should take special measure.
        ■  When mounted position altitude exceed 2000 meters, every rise 500 meters down 10% use, highest do not exceed 4500 meters.
         The pollution degree is "pollution degree 3".